Within this field the average calculated air velocity within the area under consideration can be overrided. When not filled in , the system calculates with the Air velocity for dilution (calculated average), as specified in the area properties. This average calculated value is for indicative purposes only.
It is strongly recommended to measure the air velocity near the source of release to have a good and certain view on the dillution of possible flammable substances in the air.
For outdoor situations the dilution depends completely on the windspeed and direction. Table C.1. of IEC 60079-10-1 gives guidance on the values to be used:
En este campo se puede anular la velocidad media del aire calculada dentro de la zona considerada. Cuando no se rellena , el sistema calcula con la Velocidad del aire para la dilución (media calculada), tal y como se especifica en las propiedades del área. Este valor medio calculado es sólo para fines indicativos.
Se recomienda fuertemente medir la velocidad del aire cerca de la fuente de emisión para tener una visión buena y segura sobre la dilución de posibles sustancias inflamables en el aire.
Para situaciones al aire libre, la dilución depende completamente de la velocidad y dirección del viento. La tabla C.1. de la norma IEC 60079-10-1 orienta sobre los valores que deben utilizarse: