zone.non-hazardous-zone-2-ne.details

The standard specifies the following requirements for applying a non-hazardous NE classification:

The criteria for a zone NE classification should be based on the following factors (see section 4.4.2 of IEC 60079-10-1:2020 Edition 3.0):

  1.  Ignition would not result in sufficient pressure to cause harm either due to the pressure wave or due to damage that could cause flying objects or particles e.g. broken glass from windows.
  2. Ignition would not result in sufficient heat to cause harm or a fire from surrounding materials.
  3. For gas distributed at pressures above 1 000 kPag (10 barg) consideration shall be given to a specific risk assessment
  4. A zone NE shall not be applied to gas distributed at pressures above 2 000 kPag (20 barg) unless a specific detailed risk assessment can document otherwise.

La norma especifica los siguientes requisitos para aplicar una clasificación NE no peligrosa:

Los criterios para una clasificación NE de zona deben basarse en los siguientes factores (véase la sección 4.4.2 de IEC 60079-10-1:2020 Edition 3.0):

  1.  La ignición no daría lugar a una presión suficiente para causar daños, ya sea debido a la onda de presión o debido a daños que podrían causar objetos o partículas en vuelo, por ej.Por ejemplo, la rotura de cristales de ventanas.
  2. La ignición no produciría calor suficiente para causar daños o un incendio de los materiales circundantes.
  3. Para el gas distribuido a presiones superiores a 1 000 kPag (10 barg) se tendrá en cuenta una evaluación de riesgos específica
  4. No se aplicará una zona NE al gas distribuido a presiones superiores a 2 000 kPag (20 barg) a menos que una evaluación de riesgos detallada específica pueda documentar lo contrario.
.